H1Z2Z2-K

H1Z2Z2-K 
  
STANDARD: TS EN 50618
TECHNICAL DATA:Max. Operating Temp.: 90 °C 
 Minimum Bending Radius: 4xD
 Max. Short Circuit Temp.: 250 °C
 Rated Voltage: 1,0/1,0 V
CONSTRUCTION:                  1. Flexible Copper Conductor 
 2. Low Smoke Cross-Linked Zero Halogen Insulation   
 3. Low Smoke Cross-Linked Zero Halogen Outer Sheath

 

APPLICATION

Solar cables are designed as connection cables between solar panels and inverters for use in both open and closed space applications. They are used in places where human life and valuable equipment need to be protected.

Contact Form

Please enable JavaScript in your browser to complete this form.

 

H1Z2Z2-K
TECHNICAL TABLE

Nominal Cross Section (mm²)Overall Diameter (mm)Net Weight (kg/km) Aprox.Standard Delivery Length (m)Conductor DC Resistance at 20˚C (ohm/km)Current Carrying Capacity in ConduitCurrent Carrying Capacity in Air
1.52.630100013.73029
2.55.14110008.214139
45.65610005.095552
66.27610003.397067
107.612110001.959893
169.117910001.24132125
2511.127510000.795176167
3512.727810000.565218207
5014.853110000.393276262
7016.972810000.277347330
9519.194210000.21416395
12021.1119710000.164488464
15023.6150810000.132566538
18526.4179710000.108644612
24029.5237710000.0817775736