Koç Kablo Ind. Trade Ltd. Co.

Contact
Address:
Ramazanoğlu Mah. Kaynarca Cad. No: 25 Pendik / İSTANBUL

YAVV
NAYY

YAVV (TS), NAYY (IEC, VDE)
  
STANDARD: IEC 60502-1,  VDE 0271
TECHNICAL DATA:Max. Operating Temp.: 70 °C 
 Minimum Bending Radius: 15xD
 Max. Short Circuit Temp.: 160 °C
 Rated Voltage: 0.6/1 kV
 Test Voltage: 3,5 kV
CONSTRUCTION:                  1. Stranded Aluminium Conductor
 2. PVC Insulation
 3. Filler
 4. PVC Outer Sheath

APPLICATION

It is preferred especially in areas such as underground cable installations, intra-city and inter-city power transmission lines, power distribution in industrial facilities, and fixed installation applications. It provides an effective solution in places where durability and long-term use are needed, including residential complexes, factories, power plants, and infrastructure connections for shopping centers.

Contact Form

Please enable JavaScript in your browser to complete this form.

 

YAVV NAYY
TECHNICAL TABLE

Nominal Cross Section (mm²)Overall Diameter (mm)Net Weight (kg/km) Aprox.Standard Delivery Length (m)Conductor DC Resistance at 20˚C (ohm/km)Current Carrying Capacity in ConduitCurrent Carrying Capacity in Air
1x2511.517910001.2--
1x3512.722410000.868--
1x5014.629210000.641118 - 104149 - 128
1x7016.136710000.433150 - 133192 - 166
1x9518.749910000.32181 - 161235 - 203
1x12020.458610000.253210 - 186273 - 237
1x15022.571810000.206234 - 204316 - 274
1x18524.987610000.164266 - 230363 - 316
1x24028.211385000.125312 - 269430 - 375
1x30031.313905000.1358 - 306497 - 434
2x1617.845810001.914861
2x2522.269610001.26278
2x3524.686710000.8687796
2x5028.6116510000.64192117
3x1016.740510003.08--
3x1618.952310001.914861
3x2523.678410001.26278
3x3526.29845000.8687796
3x5030.513225000.64192117
3x703416765000.443116150
3x9539.522785000.32139183
3x12042.926645000.253160212
3x15047.733045000.206176245
3x18552.940535000.164199280
3x24060.252895000.125232330
3x3006765085000.1265381
Nominal Cross Section (mm²)Overall Diameter (mm)Net Weight (kg/km) Aprox.Standard Delivery Length (m)Conductor DC Resistance at 20˚C (ohm/km)Current Carrying Capacity in ConduitCurrent Carrying Capacity in Air
3x25+162588410001,20/1,916278
3x35+1627.6109310000,868/1,917796
3x50+2532.414805000,641/1,2092117
3x70+353618645000,443/0,868116150
3x95+5041.725075000,320/0,641139183
3x120+7045.930265000,253/0,443160212
3x150+7050.135375000,206/0,443176245
3x185+9556.245365000,164/0,320199280
3x240+12063.357865000,125/0,253232330
3x300+15070.371745000,100/0,206265381
4x2526.196410001.26278
4x3529121110000.8687796
4x5033.816255000.64192117
4x7037.820765000.443116150
4x9543.828075000.32139183
4x12047.732985000.253160212
4x1505442265000.206176245
4x18559.751525000.164199280
4x2406867415000.125232330
4x30075.382305000.1265381
5x1022.272810003.08--
5x1625.298610001.914861
5x2531.8144810001.26278
5x3535.4182210000.8687796
Category Products