NA2XRH (IEC, VDE) | |
STANDARD: | TS HD 604, VDE 0276 |
TECHNICAL DATA: | Max. Operating Temp.: 90 °C |
Minimum Bending Radius: 15xD | |
Max. Short Circuit Temp.: 250 °C | |
Rated Voltage: 0,6/1 kV | |
Test Voltage: 3,5 kV | |
CONSTRUCTION: | 1. Stranded Aluminium Conductor |
2. XLPE Insulation | |
3. Filler | |
4. Galvanized Round Steel Wires | |
5. HFFR Outer Sheath |
APPLICATION
It is suitable for use in places with high human traffic and where fire safety is crucial, such as refineries, hotels, schools, tunnels, skyscrapers, hospitals, and densely populated business centers. It is an ideal solution to safely meet energy needs in places with critical data infrastructure, such as data processing centers.
Nominal Cross Section (mm²) | Overall Diameter (mm) | Net Weight (kg/km) Aprox. | Standard Delivery Length (m) | Conductor DC Resistance at 20˚C (ohm/km) | Current Carrying Capacity in Conduit | Current Carrying Capacity in Air |
---|---|---|---|---|---|---|
1x25 | 15.5 | 400 | 1000 | 1.2 | 73 - 62 | 89 - 78 |
1x35 | 17.5 | 600 | 1000 | 0.868 | 90 - 77 | 111 - 96 |
1x50 | 19.5 | 700 | 1000 | 0.641 | 125 - 110 | 133 - 128 |
1x70 | 21 | 850 | 1000 | 0.433 | 160 - 140 | 173 - 166 |
1x95 | 23.5 | 1100 | 1000 | 0.32 | 195 - 170 | 212 - 203 |
1x120 | 25 | 1250 | 1000 | 0.253 | 226 - 197 | 247 - 237 |
1x150 | 27 | 1450 | 1000 | 0.206 | 261 - 227 | 287 - 274 |
1x185 | 29.5 | 1650 | 1000 | 0.164 | 298 - 259 | 330 - 316 |
1x240 | 32 | 1950 | 500 | 0.125 | 352 - 305 | 392 - 375 |
1x300 | 35.5 | 2500 | 500 | 0.1 | 406 - 351 | 455 - 434 |
1x400 | 39.5 | 3050 | 500 | 0.0778 | 511 - 472 | 502 - 507 |
1x500 | 43 | 3550 | 500 | 0.0605 | 591 - 546 | 582 - 590 |
2x25 | 25 | 1270 | 1000 | 1.2 | 101 | 108 |
3x25 | 26 | 1300 | 1000 | 1.2 | 90 | 97 |
3x35 | 28.6 | 1550 | 500 | 0.868 | 112 | 120 |
3x50 | 31 | 1800 | 500 | 0.641 | 136 | 146 |
3x70 | 36 | 2600 | 500 | 0.443 | 174 | 187 |
3x95 | 40 | 3300 | 500 | 0.32 | 211 | 227 |
3x120 | 44 | 3850 | 500 | 0.253 | 245 | 263 |
3x150 | 50 | 4900 | 500 | 0.206 | 283 | 304 |
3x185 | 55 | 5750 | 500 | 0.164 | 323 | 347 |
3x240 | 61 | 7150 | 500 | 0.125 | 382 | 409 |
3x300 | 66 | 8000 | 500 | 0.1 | 440 | 471 |
Nominal Cross Section (mm²) | Overall Diameter (mm) | Net Weight (kg/km) Aprox. | Standard Delivery Length (m) | Conductor DC Resistance at 20˚C (ohm/km) | Current Carrying Capacity in Conduit | Current Carrying Capacity in Air |
---|---|---|---|---|---|---|
3x25+16 | 27 | 1400 | 1000 | 1,20 - 1,91 | 90 | 97 |
3x35+16 | 29 | 1600 | 1000 | 0,868 - 1,91 | 112 | 120 |
3x50+25 | 32 | 1950 | 500 | 0,641 - 1,20 | 136 | 146 |
3x70+35 | 37.5 | 2900 | 500 | 0,443 - 0,868 | 174 | 187 |
3x95+50 | 41.5 | 3500 | 500 | 0,320 - 0,641 | 211 | 227 |
3x120+70 | 45.5 | 4200 | 500 | 0,253 - 0,443 | 245 | 263 |
3x150+70 | 51.5 | 5300 | 500 | 0,206 - 0,443 | 283 | 304 |
3x185+95 | 57 | 6200 | 500 | 0,164 - 0,320 | 323 | 347 |
3x240+120 | 64 | 7600 | 500 | 0,125 - 0,253 | 382 | 409 |
3x300+150 | 68 | 8450 | 500 | 0,100 - 0,206 | 440 | 471 |
4x25 | 28 | 1500 | 1000 | 1.2 | 90 | 97 |
4x35 | 31 | 1800 | 1000 | 0.868 | 112 | 120 |
4x50 | 34 | 2300 | 500 | 0.641 | 136 | 146 |
4x70 | 41 | 3200 | 500 | 0.443 | 174 | 187 |
4x95 | 45.5 | 3850 | 500 | 0.32 | 211 | 227 |
4x120 | 51.5 | 5100 | 500 | 0.253 | 245 | 263 |
4x150 | 56.5 | 6000 | 500 | 0.206 | 283 | 304 |
4x185 | 62 | 7000 | 500 | 0.164 | 323 | 347 |
4x240 | 68.5 | 8500 | 500 | 0.125 | 382 | 409 |
4x300 | 75 | 10000 | 500 | 0.1 | 440 | 471 |
5x25 | 30.3 | 1800 | 1000 | 1.2 | 90 | 97 |
5x35 | 34.5 | 2410 | 1000 | 0.868 | 112 | 120 |
5x50 | 39.9 | 3330 | 1000 | 0.641 | 136 | 146 |
5x70 | 45.1 | 4120 | 1000 | 0.443 | 174 | 187 |
5x95 | 50.9 | 5190 | 1000 | 0.32 | 211 | 227 |