Koç Kablo Ind. Trade Ltd. Co.

Contact
Address:
Ramazanoğlu Mah. Kaynarca Cad. No: 25 Pendik / İSTANBUL

NA2XH

NA2XH (IEC, VDE) 
  
STANDARD: TS HD 604, VDE 0276
TECHNICAL DATA:Max. Operating Temp.: 90 °C 
 Minimum Bending Radius: 15xD
 Max. Short Circuit Temp.: 250 °C
 Rated Voltage: 0,6/1 kV
CONSTRUCTION:                  1. Stranded Aluminium Conductor
 2. XLPE Insulation
 3. Filler
 4. HFFR Outer Sheath

 

APPLICATION

They are used in areas such as hotels, schools, tunnels, high-rise buildings, hospitals, power plants, data processing centers, and business centers to ensure secure energy distribution. Enhanced features against fire and high-temperature resistant XLPE insulation make these cables ideal for emergency systems and other applications requiring fire safety.

Contact Form

Please enable JavaScript in your browser to complete this form.

 

NA2XH
TECHNICAL TABLE

Nominal Cross Section (mm²)Overall Diameter (mm)Net Weight (kg/km) Aprox.Standard Delivery Length (m)Conductor DC Resistance at 20˚C (ohm/km)Current Carrying Capacity in ConduitCurrent Carrying Capacity in Air
1x2510.515010001.273 - 6289 - 78
1x351218010000.86890 - 77111 - 96
1x5013.522510000.641125 - 110133 - 128
1x7015.530510000.433160 - 140173 - 166
1x951740510000.32195 - 170212 - 203
1x1201951010000.253226 - 197247 - 237
1x1502160510000.206261 - 227287 - 274
1x1852376510000.164298 - 259330 - 316
1x240269255000.125352 - 305392 - 375
1x3002811555000.1406 - 351455 - 434
1x4003114805000.0778511 - 472502 - 507
1x5003518505000.0605591 - 546582 - 590
1x63037.826705000.0469679 - 629669 - 680
2x252160810001.29097
2x3523.476810000.868112120
2x5027101610000.641136146
3x1015.433810003.08--
3x1617.644610001.157677
3x2522.367810001.29097
3x3524.98645000.868112120
3x5028.811475000.641136146
3x7032.715075000.443174187
3x9537.319925000.32211227
3x12041.223985000.253245263
3x1504629915000.206283304
3x18551.236885000.164323347
3x2405847855000.125382409
3x30064.959445000.1440471
Nominal Cross Section (mm²)Overall Diameter (mm)Net Weight (kg/km) Aprox.Standard Delivery Length (m)Conductor DC Resistance at 20˚C (ohm/km)Current Carrying Capacity in ConduitCurrent Carrying Capacity in Air
3x16+1019.556210001,91 - 3,087677
3x25+1623.978510001,20 - 1,919097
3x35+1626.598110000,868 - 1,91112120
3x50+253113185000,641 - 1,20136146
3x70+3534.917025000,443 - 0,868174187
3x95+5039.922485000,320 - 0,641211227
3x120+7044.527745000,253 - 0,443245263
3x150+7048.732475000,206 - 0,443283304
3x185+9554.741805000,164 - 0,320323347
3x240+12061.553235000,125 - 0,253382409
3x300+15068.566265000,100 - 0,206440471
4x162150910001.917677
4x2524.783410001.29097
4x3527.6106510000.868112120
4x5031.914065000.641136146
4x7036.418685000.443174187
4x9541.424575000.32211227
4x12045.729495000.253245263
4x1505238105000.206283304
4x18557.746685000.164323347
4x24065.661095000.125382409
4x30072.974985000.1440471
5x1623.173810001.917677
5x2526.999210001.29097
5x3530.4129410000.868112120
5x5035.4173410000.641136146
5x7040.3228910000.443174187
5x9546.5309710000.32211227
Category Products