H05V-K / H07V-K (NYAF) | |
STANDARDS: | TS EN 50525-2-31, VDE 0281, IEC 60227, BS 6004 |
TECHNICAL DATA: | Max. Operating Temp.: 70 °C |
Minimum Bending Radius: 6xD | |
Max. Short Circuit Temp.: 160 °C | |
Rated Voltage: 300/500 V, 450/750 V | |
CONSTRUCTION: | 1. Flexible Copper Conductor |
2. PVC Insulation |
APPLICATION AREAS
It is generally designed for use in electrical installation pipes, above or below plaster, or similar closed systems. Uses of this cable include lighting systems, switches and control devices, production facilities and are ideal for voltages up to 1000 V AC or 750 V DC.
Nominal Cross Section (mm²) | Overall Diameter (mm) | Net Weight (kg/km) Aprox. | Standard Delivery Length (m) | Conductor DC Resistance at 20˚C (ohm/km) | Current Carrying Capacity in Conduit | Current Carrying Capacity in Air |
---|---|---|---|---|---|---|
0.5 | 2.2 | 8.5 | 100 | 39 | - | 9 |
0.75 | 2.4 | 11 | 100 | 26 | - | 15 |
1 | 2.6 | 14 | 100 | 19.5 | 11 | 19 |
Nominal Cross Section (mm²) | Overall Diameter (mm) | Net Weight (kg/km) Aprox. | Standard Delivery Length (m) | Conductor DC Resistance at 20˚C (ohm/km) | Current Carrying Capacity in Conduit | Current Carrying Capacity in Air |
---|---|---|---|---|---|---|
1.5 | 2.9 | 19 | 100 | 13.3 | 15 | 24 |
2.5 | 3.7 | 30 | 100 | 7.98 | 20 | 32 |
4 | 4.3 | 46 | 100 | 4.95 | 25 | 42 |
6 | 4.7 | 63 | 100 | 3.3 | 33 | 54 |
10 | 6.2 | 114 | 100 | 1.91 | 45 | 73 |
16 | 7.3 | 171 | 100 | 1.21 | 61 | 98 |
25 | 9.5 | 267 | 100 | 0.78 | 83 | 129 |
35 | 11 | 365 | 1000 | 0.554 | 103 | 158 |
50 | 13 | 520 | 1000 | 0.386 | 132 | 198 |
70 | 14.9 | 714 | 1000 | 0.272 | 165 | 245 |
95 | 17 | 939 | 1000 | 0.206 | 197 | 292 |
120 | 18.9 | 1182 | 1000 | 0.161 | 235 | 344 |
150 | 21.7 | 1500 | 1000 | 0.129 | - | 391 |
185 | 23.1 | 1860 | 1000 | 0.106 | - | 448 |
240 | 27.5 | 2400 | 1000 | 0.0801 | - | 528 |